Facts
Specifications, test evidence and deployment rules for OWL and ATHENA.
OWL
- Bus
- RS-485, 2-wire, connected in parallel at A, B and REF
- Protocols
- Modbus RTU and DNP3 serial
- Bus speed
- Eight standard speeds from 1200 to 115200 baud, detected from the traffic. The receiver's limit is 200 kbps.
- Character format
- 8N1, 8E1, 8O1, 8N2, detected from the traffic
- Receiver
- Galvanically isolated, wired receive-only
- Isolation gaps on the board
- Bus to logic 6.1 mm. Output to logic 6.3 mm.
- Load on the bus
- 1 k in series with each line. A shorted protection diode loads the bus with 2 k.
- Supply
- 24 V DC, under 2 W. Fused, reverse-protected, monitored.
- Processor
- RP2350 (Raspberry Pi Pico 2). No radio.
- Link to ATHENA
- One-way optocoupler, 3 wires, 230400 baud, about 3 m of cable
- Heartbeat
- Once a second, so a dead tap is never read as a quiet bus
- Front panel
- Three lights: PWR, RX, ALM. No display.
- Case
- 35 mm DIN rail, 3 modules. 54 x 90 x 58 mm.
ATHENA
- Decoding
- Modbus RTU and DNP3 serial, one protocol per bus
- Platform
- Raspberry Pi 3B or 4. One static binary, 4.1 MB.
- Storage
- SQLite on the Pi. A power cut loses at most the last second of frames.
- Retention
- Frames: 7 days or 5 million rows. Detections, baseline revisions and the audit log are kept.
- Output
- JSON lines, or RFC 5424 syslog over UDP or TCP
- Accounts
- Named local accounts. Three roles. Audit log.
- Network
- Needs no internet access.
Test evidence
- Board: no design-rule errors, no unconnected pads.
- Case: every part fit-checked, no collisions.
- Firmware: 60 tests pass. Bus speed and format detected correctly at every supported setting.
- Collector: 87 tests pass, end to end, across Modbus RTU and DNP3.
- Both hold up under random and damaged input without crashing.
Deployment rules
- OWL connects in parallel only. It never sits in series with a bus.
- Bench bus first. Plant bus later.
- Get the asset owner's approval and a change record before anything touches live equipment.
- Protect the 24 V feed as the panel design requires. The board's own fuse does not replace that.
- The case is PETG and is not flame rated. Keep it out of cabinets that run hot.